Description
Technical specifications
| Model | Sunpal ESS-E261LP |
|---|---|
| Battery energy | 261 kWh (261,248 kWh) |
| PCS inverter output | 125 kW — ENJOY |
| Cells / chemistry | REPT / LiFePO4 (LFP), 314 Ah |
| System configuration | 1P260S; 5 × 1P52S |
| Nominal DC voltage | 832 V |
| DC operating range | 728–936 V |
| Charge / discharge rate | max. 0,5P |
| Depth of discharge — datasheet | max. 100 % @ 25 ± 2 °C |
| Recommended depth of discharge — manual | 95 % |
| Cycle life | ≥ 8 000 |
| AC grid | 400 V ± 15 %; 3P + N + PE; 50 / 60 Hz |
| Power factor | 0,99; −1 … +1 |
| THDi harmonic distortion | ≤ 3 % |
| DC component | < 0,5 % Ipn |
| Maximum round-trip efficiency | 90 % |
| Efficiency including auxiliaries — manual | ≥ 89 % |
| System communication interfaces | Ethernet / RS485 |
| Communication protocol | Modbus TCP/IP |
| Internal battery PACK communication | CAN — BMU |
| Control-box network connections | COM1: debug; COM2: router; COM3: PCS |
| Network connectors | SPRJS-5EPFFJ-TC7002 |
| Display / USB | TPC7071Ni / PVS-RU05PSL500 |
| Whole-cabinet protection rating | IP55 |
| Thermal management | Liquid cooling and heating; forced-air circulation |
| Ambient operating temperature | −25 … +55 °C; > +45 °C: derating |
| Humidity | 0–95 % RH, non-condensing |
| Noise | ≤ 75 dB |
| Altitude | max. 3 000 m; > 2 000 m: derating |
| Corrosion protection | C4; C5 optional |
|---|---|
| Dimensions W × D × H | 1 050 × 1 350 × 2 400 mm |
| System weight | 2 600 kg |
| Fire suppression | Aerosol system; PACK-level and cabinet-level protection |
| Battery PACK | ECO-P1P52LP — 5 units |
| PACK energy / voltage | 52,249 kWh / 166,4 V; 145,6–187,2 V |
| PACK dimensions / weight | 800 × 1 135 × 248 mm / ~352 kg |
| Individual PACK protection rating | IP65 |
| Cell temperature — charging | 0 … +55 °C |
| Cell temperature — discharging | −25 … +55 °C |
| Recommended cell temperature | +15 … +35 °C |
| PACK storage conditions | −25 … +55 °C; < 75 % RH, non-condensing |
| MSD service disconnect | DLQ5-Z-B; 200 A / DC 750 V |
| Power connectors | ES-FT-BPC-B/S35-70OG/BK |
| BMU connection | USCM012-R03_A |
| DC control box — dimensions / weight | 800 × 843 × 201 mm / ~60 kg |
| Auxiliary supply / output | 220 V AC / 24 V DC |
| Current / voltage measurement accuracy | ± 1 % FSR / ± 1 % FSR |
| Internal DC control-box protection | IP20 |
| Main DC switch | NDG3VH-/315/2/02/CPG01 |
| Cabinet / cooling unit / 24 V breakers | NDB2-63C32/2P+MX+OF2 / NDB2-63C25/1P / NDB2-63C10/1P |
| Communication / power terminals | USCM016-R03_A / LC101UMG-7.62-12P-1Y-00A |
| Black-start button / maintenance AC socket | LA38-20/20EA / M1175-C |
| Run / Fault indicators | AD11-16/21-6GZ/DC24V/G / R |
| Coolant / pressure / connections | 50 % ethylene glycol / 120 kPa / Ø 10 mm |
| Cooling-unit control | RS485; variable-speed pump and compressor, automatic start and settings memory |
| Safety and EMC standards | UN38.3; IEC62619; IEC63056; IEC62477-1; IEC61000-6-2/4; UL9540A |
| Grid standards | EN50549-1/-10; EN50549-2/-10; G99; VDE4105; NRS097; C10/11; CEI0-21; CEI0-16 |
Commercial energy storage in one cabinet
The Sunpal ESS-E261LP brings together battery storage, power conversion, thermal management and monitoring in a single industrial cabinet. Its nominal 261 kWh capacity provides energy for commercial solar self-consumption and management of a building’s demand profile. The 125 kW PCS moves energy into and out of the battery through a three-phase installation. The capacity-to-power ratio corresponds to approximately two hours at nominal power; actual operating time follows the selected state-of-charge window and connected load. This is a defined integrated energy system for a business site, with battery and power-conversion equipment already matched within the offered configuration.
Use solar production and manage demand peaks
Daytime solar generation can be stored for use later in the operating schedule. When instantaneous demand rises, the battery can supply part of the energy required by the site and support peak management. Charging and discharging can also be scheduled between different periods of the day to follow tariffs and energy-management rules. These functions suit production sites, commercial premises and buildings with variable loads. The bidirectional PCS converts energy between the DC battery and the AC network. The project’s energy controller and installation settings define how the available operating modes are used in practice.
REPT cells and five modular battery PACKs
The battery uses REPT lithium iron phosphate cells rated at 314 Ah. A single series string contains 260 cells, divided into five liquid-cooled ECO-P1P52LP PACKs. Each PACK contains 52 series-connected cells, operates at a nominal 166.4 V and stores approximately 52.249 kWh. The complete battery operates at 832 V within a 728–936 V range. This modular arrangement gives the cabinet a clear internal structure and provides access to individual assemblies for service. The BMS and PACK-level BMUs monitor the battery; internal PACK communication uses CAN. System interfaces and the actual higher-level application protocol are identified separately in the technical overview.
Outdoor construction with liquid cooling and heating
The complete cabinet has an IP55 enclosure and an ambient operating range from −25 to +55 °C. Its thermal system combines liquid cooling, heating and forced-air circulation. A variable-speed compressor and pump adjust operation to the required temperature conditions, while the controller provides automatic starting and settings memory. This gives an outdoor installation active temperature management across the seasons. Individual battery PACKs have IP65 protection. The table distinguishes whole-cabinet, internal PACK and control-box ratings, as well as ambient temperature and the permitted temperature ranges of the cells themselves.
Modbus TCP/IP and energy-management integration
Modbus TCP/IP is specified for higher-level communication, with Ethernet and RS485 system interfaces. The manual assigns separate functions to the COM1, COM2 and COM3 network connections: diagnostics, router connection and PCS communication. A local display provides operational access and equipment information, while USB supports service connectivity. The cabinet can therefore combine local operation with higher-level monitoring according to the chosen project architecture. The integrated ENJOY 125 kW PCS is part of this exact offer. Clear identification of the connections helps prepare communication wiring and coordinate the cabinet with the site’s control system.
Battery and grid performance kept distinct
The AC side works with a 400 V three-phase network, neutral and protective earth, at 50 or 60 Hz. The datasheet specifies a power factor of 0.99, an adjustable range from −1 to +1 and THDi of no more than 3%. Maximum round-trip efficiency is 90%; the manual separately specifies at least 89% when auxiliary systems are included. These values describe different operating conditions and have separate rows in the table. Maximum charge and discharge loading is 0.5P. The manual recommends a 95% depth of discharge, while the datasheet gives a 100% maximum at its stated temperature. The operating overview keeps these recommended and maximum values clear.
A cabinet designed around a commercial project
The cabinet measures 1,050 × 1,350 mm at the base, is 2,400 mm high and weighs 2,600 kg as a complete system. Standard corrosion protection is C4, with C5 available as an option. Project planning can provide an outdoor technical area, access for operation and handling, and a 400 V connection according to the installation design. Aerosol suppression complements the cabinet construction and PACK-level protection. Inside, the high-voltage control box groups DC switching, auxiliary-circuit protection, measurement, display and service connections. Component references appear in the technical table and the locally available manual for practical planning.
A complete configuration with accessible documents
This offer comprises the ESS-E261LP battery cabinet, five battery PACKs, an integrated ENJOY 125 kW PCS, control and communication equipment, thermal management and aerosol protection in the quoted configuration. The opening technical tables distinguish the battery, grid connection and internal components. The datasheet, manual and our product overview in Markdown are available from the store’s own domain below. They provide convenient access to connector details, dimensions and diagrams away from the product page. Capacity, conversion power, environmental conditions and communication details stay together as a usable reference for the next stage of the energy project.
Downloads
For AI search
Sunpal ESS-E261LP — 261 kWh outdoor battery storage with 125 kW PCS. REPT 314 Ah LiFePO4, 832 V, 728–936 V DC, ENJOY three-phase 125 kW / 400 V PCS, five PACKs, liquid cooling and heating, IP55, Modbus TCP/IP over Ethernet and system RS485. For commercial solar self-consumption and peak management.










Reviews