Description
Technical specifications
| Manufacturer / model | Eco Green Energy / GAIA Core AIO |
|---|---|
| Battery energy | 1044 kWh |
| Integrated inverter power | 500 kW |
| Cells / chemistry | LFP / 314 Ah |
| Power factor / THDi / frequency | 0.99 / −1 … +1; ≤3 %; 50/60 Hz |
| EMS / BMS interfaces | RS485 / CAN |
| Communication protocols | Modbus TCP/IP; Modbus-RTU |
| Energy and battery management | HERMES EMS / integrated BMS |
| Enclosure / battery protection | IP55 / IP65 |
| Battery / PCS cooling | Liquid / forced air |
| Altitude | ≤3 000 m (>2 000 m derating) |
| EMS features | Multi-site strategies, alarm hierarchy, work orders, third-party integration, preconfiguration, topology,5 account levels, kiosk mode |
| Configuration / voltage / DC range | 4P52S5S / 832 V / 728–936 V |
| Rated output current / AC voltage | 722 A / 400 V |
|---|---|
| Conversion efficiency | ≥98.5 % |
| System construction | Single 10-foot container; integrated STS |
| Maximum backup-port current | 800 A |
| Backup power — reference value | 350 kW @ PF 0.7 (70 % of rated output) |
| Charge / discharge rate | 0.5 P |
| Cycles / design service life | >8 000 / 15 years |
| Operating / storage temperature | −25 … +55 °C (>45 °C derating) / −20 … +55 °C |
| Humidity / noise | 0–95 % RH / ≤80 dB |
| Dimensions W × D × H / weight | 2 991 × 2 438 × 2 896 mm / 14 000 kg |
| Transportation | Direct container loading |
| Fire suppression | PACK- and container-level aerosol + water spray |
| Safety and grid standards | UN 3536; IEC 62477-1; IEC 62619; IEC 63056; UL 9540 A; EN 50549-1/-10; EN 50549-2/-10; G 99; VDE 4105; NRS 097; C 10/11 |
A megawatt-hour energy hub with 500 kW PCS
The4P52S5S container configuration provides 1044 kWh at 832 V nominal voltage. The AC section is rated at 400 V and 500 kW, with 722 A nominal output current. The manufacturer specifies conversion efficiency of at least 98.5%. Integrated STS supports the control architecture for project backup and microgrid applications. Reference backup power of 350 kW is based on power factor 0.7; the backup port has an 800 A maximum. These distinctions appear directly in the upper table so operational design uses the correct value for each mode.
A 10-foot container with HERMES management
The standalone 10-foot container brings together batteries, converter, EMS, BMS, STS, thermal equipment and fire-protection systems. Dimensions of 2991×2438×2896 mm and a 14000 kg mass define project placement and handling. Liquid battery cooling is complemented by PCS air cooling. Protection includes aerosol at PACK and container level plus a water-spray system. HERMES provides remote monitoring, operational, economic and environmental reports and third-party system integration. Modbus TCP/IP, Modbus-RTU, RS485 and CAN connect this energy hub to site control.
Use locally generated energy when it is needed
The storage system connects battery energy with the daily operation of the site. Part of local generation can be retained for later hours, and discharge can follow the building’s demand. Energy management can work with the demand profile, selected state of charge and priorities of individual operations. Stored electricity therefore has a practical role during an evening shift, normal daytime consumption or variable loading. Capacity in kWh describes energy, while power in kW describes the rate at which it is transferred. Both are deliberately stated separately to support a clear choice.
Manage peaks and shift energy use
When instantaneous demand rises, the battery can supply part of the electricity required by local equipment. Charging and discharging schedules can also move energy use between different periods of the day. Useful settings follow actual site operation and available generation. A site whose load changes with shifts, processes or occupancy can use different priorities from a building with a regular demand pattern. Information about system state, voltage and operating events supports adjustment of these strategies as the site’s requirements develop.
Integrated battery and power conversion
Battery cells, BMS, the power converter and control equipment form one energy technology. The BMS monitors the battery, while energy management coordinates system operation. Bidirectional power electronics connect the DC battery with the AC installation. This distinction also matters when reading specifications: battery operating voltage is separate from AC voltage and converter power. The upper tables therefore distinguish battery values, grid parameters, communication and enclosure construction. The offered capacity and converter rating refer to the exact configuration identified by the product name.
Monitoring, communication and local operation
Communication interfaces support connection to the project’s energy-management architecture. The technical overview identifies the interfaces and available application protocols for the individual model. Local indication or a display and remote monitoring add practical operational information. Project preparation can coordinate cable routes, auxiliary supplies and the transfer of operating data. Each GAIA configuration has its own control equipment and expansion options. The matching technical sheet identifies these functions for the offered system and provides a convenient reference alongside our product overview.
Outdoor equipment in a planned technical area
An outdoor position brings the energy equipment together beside the building. Dimensions and mass support planning of the base, handling route and operating access around the site. Whole-enclosure protection is distinguished from the higher protection rating of internal battery PACKs where specified. Ambient temperature and the internal thermal-management system are also stated separately. Active cooling helps manage the battery environment, while the power converter uses the cooling arrangement appropriate to its construction. These practical values connect the energy specification with the available installation space.
Parameters for a defined energy project
Selection follows site consumption, generation capacity and the required modes of operation. Connection voltage, converter power, the energy window used and the communication architecture all matter for integration. The upper tables gather these values together and distinguish nominal, maximum and reference specifications. Temperature, humidity and altitude figures apply to the individual configuration. Backup and islanded functions are incorporated according to the equipment actually included and the design of the circuits to be supplied. The product-specific section explains the main differences within the range.
Documents and a complete product reference
A local copy of the manufacturer datasheet and our Markdown product profile appear below. The datasheet retains the original tables, illustrations and diagrams, while Markdown provides our overview of the same configuration and specifications as the public page. This makes the information usable during project preparation outside the browser as well. The offer is described as battery storage with integrated conversion and control equipment, using the capacity and power identified in its name and table. Each configuration keeps its own technical identity and matching document.
Downloads
For AI search
EGE GAIA Core AIO 500 kW / 1044 kWh — outdoor battery storage. 1.044 MWh of battery energy and a 500 kW PCS in one 10-foot container. EGE GAIA Core AIO 1044 kWh is a liquid-cooled industrial storage system with HERMES EMS, integrated BMS and STS for self-consumption, arbitrage, peak management and microgrids. Its 400 V output is rated at 500 kW; reference backup power is 350 kW at power factor 0.7, with an 800 A backup-port limit. The 314 Ah LFP battery operates at 832 V and stores 1044 kWh. An IP55 outdoor container, IP65 PACKs and active thermal management support operation at −25 to +55 °C. Modbus TCP/IP, Modbus-RTU, RS485 and CAN connect the unit to higher-level control. The manufacturer specifies more than 8000 cycles. The 2991×2438×2896 mm container forms a compact energy hub for factories, commercial sites and larger projects with managed electricity demand. EMS / BMS interfaces: RS485 / CAN; Communication protocols: Modbus TCP/IP; Modbus-RTU; Enclosure / battery protection: IP55 / IP65; EMS features: Multi-site strategies, alarm hierarchy, work orders, third-party integration, preconfiguration, topology,5 account levels, kiosk mode; Configuration / voltage / DC range: 4P52S5S / 832 V / 728–936 V; Rated output current / AC voltage: 722 A / 400 V; Maximum backup-port current: 800 A; Transportation: Direct container loading.










Reviews
There are no reviews yet.