Store energy. Every way.™

Helping with technology for more than 25 years.More than 25 years on the market

EGE GAIA Core AIO 125 kW / 261 kWh — outdoor battery storage

1 492 379 Kč incl. VAT

Seller: Tomorrow Systems® s.r.o.

261 kWh of energy with an integrated 125 kW PCS: EGE GAIA Core AIO is an outdoor AC storage system for commercial solar self-consumption and demand-peak management. Its 314 Ah LFP cells form an 832 V battery, with a 400 V three-phase output for the site installation. A liquid cooler with 5 kW cooling capacity and PCS air cooling actively manage temperature. The cabinet is IP55, internal battery PACKs are IP67 and the ambient operating range is −30 to +50 °C. Integrated EMS and BMS, an LCD and Modbus and MQTT protocols support monitoring and connection to site energy management. The modular configuration supports up to 20 systems in parallel on-grid or 5 off-grid. A 1120×1350×2420 mm cabinet provides a compact, integrated solution for larger buildings, commercial properties and industrial energy projects.

24–40 days

Enquiry

Description

Technical specifications

Manufacturer / modelEco Green Energy / GAIA Core AIO
Battery energy261 kWh
Integrated inverter power125 kW
Cells / chemistryLFP / 314 Ah
Cell voltage / PACK / system3.2 V / 1P52S / 1P260S
Voltage / DC range832 V / 728–936 V
AC output / frequency400 V / 50 Hz, 60 Hz ± 2.5 Hz
Charge / discharge rate0.5 P @ 25 °C
BMS / EMS / HMIIntegrated BMS and EMS, LCD
Ports / communication protocolsRS485, Ethernet / Modbus, MQTT
Parallel connection20 on-grid / 5 off-grid
Cabinet / battery PACK protectionIP55 / IP67
Thermal management5 kW liquid cooler + PCS air cooling
Operating / storage temperature−30 … +50 °C (>45 °C derating) / −30 … +60 °C
Humidity / altitude5–95 % RH / ≤2 000 m (>2 000 m derating)
Dimensions L × W × H / weight1 120 × 1 350 × 2 420 mm / 2 600 kg
Control box / monitoringIntegrated high-voltage and combining equipment; LCD and EMU
Fire suppressionSmoke, heat and Li-ion detection; aerosol and ventilation; PACK isolation,1.5 h resistance
Standards / manufacturer warrantyIEC 62619; UN 38.3; IEC 62477; IEC 61000; GB/T 36276 / 5 years

261 kWh and 125 kW for commercial AC integration

The 314 Ah LFP cells form a1P260S system with 832 V nominal voltage. The 728–936 V operating range applies to the battery; AC output is 400 V. The 125 kW PCS is included in this priced configuration together with EMS, BMS and the high-voltage control equipment. The 0.5 P charge/discharge rating is specified at 25 °C. In a project with an existing or separately selected solar inverter, this cabinet integrates on the AC side and follows the site charging schedule.

Liquid cooling, Modbus and MQTT

The integrated liquid cooler provides 5 kW of cooling capacity; the PCS uses air cooling. Whole-cabinet protection is IP55 and battery PACK protection is IP67. The ambient operating range is −30 to +50 °C with derating above 45 °C, and storage is −30 to +60 °C. RS485 and Ethernet are accompanied by Modbus and MQTT for control and monitoring. A local LCD provides information during operation. The documentation specifies up to 20 parallel systems on-grid and 5 off-grid. Smoke, heat and Li-ion detection, aerosol suppression and PACK isolation complement the construction.

Use locally generated energy when it is needed

The storage system connects battery energy with the daily operation of the site. Part of local generation can be retained for later hours, and discharge can follow the building’s demand. Energy management can work with the demand profile, selected state of charge and priorities of individual operations. Stored electricity therefore has a practical role during an evening shift, normal daytime consumption or variable loading. Capacity in kWh describes energy, while power in kW describes the rate at which it is transferred. Both are deliberately stated separately to support a clear choice.

Manage peaks and shift energy use

When instantaneous demand rises, the battery can supply part of the electricity required by local equipment. Charging and discharging schedules can also move energy use between different periods of the day. Useful settings follow actual site operation and available generation. A site whose load changes with shifts, processes or occupancy can use different priorities from a building with a regular demand pattern. Information about system state, voltage and operating events supports adjustment of these strategies as the site’s requirements develop.

Integrated battery and power conversion

Battery cells, BMS, the power converter and control equipment form one energy technology. The BMS monitors the battery, while energy management coordinates system operation. Bidirectional power electronics connect the DC battery with the AC installation. This distinction also matters when reading specifications: battery operating voltage is separate from AC voltage and converter power. The upper tables therefore distinguish battery values, grid parameters, communication and enclosure construction. The offered capacity and converter rating refer to the exact configuration identified by the product name.

Monitoring, communication and local operation

Communication interfaces support connection to the project’s energy-management architecture. The technical overview identifies the interfaces and available application protocols for the individual model. Local indication or a display and remote monitoring add practical operational information. Project preparation can coordinate cable routes, auxiliary supplies and the transfer of operating data. Each GAIA configuration has its own control equipment and expansion options. The matching technical sheet identifies these functions for the offered system and provides a convenient reference alongside our product overview.

Outdoor equipment in a planned technical area

An outdoor position brings the energy equipment together beside the building. Dimensions and mass support planning of the base, handling route and operating access around the site. Whole-enclosure protection is distinguished from the higher protection rating of internal battery PACKs where specified. Ambient temperature and the internal thermal-management system are also stated separately. Active cooling helps manage the battery environment, while the power converter uses the cooling arrangement appropriate to its construction. These practical values connect the energy specification with the available installation space.

Parameters for a defined energy project

Selection follows site consumption, generation capacity and the required modes of operation. Connection voltage, converter power, the energy window used and the communication architecture all matter for integration. The upper tables gather these values together and distinguish nominal, maximum and reference specifications. Temperature, humidity and altitude figures apply to the individual configuration. Backup and islanded functions are incorporated according to the equipment actually included and the design of the circuits to be supplied. The product-specific section explains the main differences within the range.

Documents and a complete product reference

A local copy of the manufacturer datasheet and our Markdown product profile appear below. The datasheet retains the original tables, illustrations and diagrams, while Markdown provides our overview of the same configuration and specifications as the public page. This makes the information usable during project preparation outside the browser as well. The offer is described as battery storage with integrated conversion and control equipment, using the capacity and power identified in its name and table. Each configuration keeps its own technical identity and matching document.

Downloads

For AI search

EGE GAIA Core AIO 125 kW / 261 kWh — outdoor battery storage. 261 kWh of energy with an integrated 125 kW PCS: EGE GAIA Core AIO is an outdoor AC storage system for commercial solar self-consumption and demand-peak management. Its 314 Ah LFP cells form an 832 V battery, with a 400 V three-phase output for the site installation. A liquid cooler with 5 kW cooling capacity and PCS air cooling actively manage temperature. The cabinet is IP55, internal battery PACKs are IP67 and the ambient operating range is −30 to +50 °C. Integrated EMS and BMS, an LCD and Modbus and MQTT protocols support monitoring and connection to site energy management. The modular configuration supports up to 20 systems in parallel on-grid or 5 off-grid. A 1120×1350×2420 mm cabinet provides a compact, integrated solution for larger buildings, commercial properties and industrial energy projects. Cell voltage / PACK / system: 3.2 V / 1P52S / 1P260S; Voltage / DC range: 832 V / 728–936 V; BMS / EMS / HMI: Integrated BMS and EMS, LCD; Ports / communication protocols: RS485, Ethernet / Modbus, MQTT; Cabinet / battery PACK protection: IP55 / IP67.

Additional information

Weight2600 kg
Dimensions112 × 135 × 242 cm

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.

0
0
Your Cart