Store energy. Every way.™

Solis S5-GC60K — 60 kW three-phase grid inverter, 6 MPPT, IP66

60 766 Kč incl. VAT

Ask about this product

High-output PV for commercial and industrial sites with flexible array grouping. Solis S5-GC60K delivers 60 kW rated output to a three-phase grid and connects up to 12 strings through 6 independent MPPTs. Each tracker supports 32 A and a 180–1000 V operating range. Up to 98.7 % efficiency, intelligent fan cooling, IP66 and C5 corrosion resistance support demanding installations at suitable locations. String monitoring and I/V scanning provide insight into generation. A compatible meter adds export control and suitable Solis monitoring enables a 24-hour consumption view. The practical 16-pin COM combines metering, multi-inverter communication and logic control. This offer includes the DC switch and standard connection components.

Available on back-order

SKU: SOLIS-S5-GC60K
Category:
Tags: , , ,
Značky:

Description

Technical specifications

Manufacturer Solis / Ginlong Technologies
Model S5-GC60K
Type and role Three-phase grid-connected PV inverter
Offered configuration Standard 400V model with 6 MPPTs and DC switch
Operating configuration PV array and three-phase utility grid
Maximum DC voltage 1100 V
Rated DC voltage 600 V
Start-up voltage 195 V
MPPT range 180–1000 V
Full-load MPPT range 550–850 V
Maximum input current per MPPT 32 A / MPPT
Maximum short-circuit current per MPPT 40 A / MPPT
Independent MPPT count 6
Maximum PV string count 12
Strings per MPPT 2 / MPPT
Rated AC power 60000 W
Maximum AC power 66000 W
Maximum apparent AC power 66000 VA
Grid conductors 3 / N / PE
Rated grid voltage 220 / 380 V; 230 / 400 V
Rated frequency 50 / 60 Hz
Rated current at 380/400 V 91.2 / 86.6 A
Maximum AC current 100.3 A
Power factor >0.99; adjustable 0.8 leading to 0.8 lagging
THDi <3 %
Maximum efficiency 98.7 %
European efficiency 98.3 %
Topology Transformerless
Night consumption <1 W
DC polarity protection Integrated function
Short-circuit protection Integrated function
AC overcurrent protection Integrated function
Surge protection DC Type II / AC Type II
Grid monitoring Integrated function
Anti-islanding protection Integrated function
Temperature protection Integrated function
Multi-peak MPPT scanning Integrated function
DC switch Integrated function
AFCI 2.0 arc protection Optional configuration
DC connectors MC4
AC terminal connection OT terminal block up to 70 mm²; L1 / L2 / L3 / N / PE
AC — phase / PE lugs M8 / M6
AC — neutral connection With or without neutral according to local grid requirements
Communication RS485 / USB
Communication connectors 4-pin COM for data logger; 16-pin COM for RS485, meter and DRM
COM — nut / terminals 3.5–4 Nm / 0.4–0.6 Nm
16-pin COM — DRM pins 9–12 9 DRM1/5; 10 DRM2/6; 11 DRM3/7; 12 DRM4/8
16-pin COM — supply pins 15 V+ 12 V; 16 V− GND
16-pin COM — reserved pins 5 / 8
RS485 — IN / OUT terminals 16pin COM: 3 A / 4 B IN; 6 A / 7 B OUT
RS485 — conductor / cable diameter 0.75–3 mm² / 4–6 mm
COM — conductor stripping 10–12 mm
Digital meter Compatible Solis three-phase meter with external CTs according to design
Meter — communication terminals Meter 21 A / 22 B → pins 1 A / 2 B of 16-pin COM
Remote monitoring Optional Wi-Fi / GPRS / LAN loggers and Wi-Fi / GPRS box for multiple devices
Inverter monitoring address 01–99; default 01
LCD display LCD with capacitive touch buttons
Controls ESC / UP / DOWN / ENTER
LED indicators POWER / OPERATION / ALARM
Displayed operating data PV and phase voltages/currents, power, frequency, energy, status, serial number and version
Generation history Daily, monthly and yearly energy
Alarm / warning history Latest 100 records in each history
Export control Internal EPM; Meter in Load / Meter in Grid / Consumption Monitor
Export-limit modes 01 average / 02 according to lowest-loaded phase
24-hour consumption monitoring Grid-side meter, 24H Switch and Solis monitoring
Meter failsafe Configurable alarm and generation stop on metering loss
External EPM 5G-EPM / Others-EPM according to actual device
Active and reactive power control Active/reactive output settings and grid working mode
DRM — logic interface 16pin COM: 13 RefGen / 14 Com/DRM0
DRM — response after opening Limit to 0 W within 5 s when enabled according to grid profile
Service updates HMI / DSP
Service compensation settings Output energy and voltage calibration for grid-operator requirements
String monitoring Integrated
PID recovery Optional configuration
Night reactive-power compensation Night SVG; configuration according to design
Night-function selection Select PID-recovery or night reactive-power-compensation configuration according to design
I/V curve scanning Integrated function
I/V scan — start / step / points 100–1100 V / 1–100 V / 60
Service fan test Fan Test
User-Def — grid-profile use Service configuration with grid-operator permission; L–N ranges per manual
User-Def — overvoltage OV-G-V1 / V2 220–374 V; 0.01–300 s
User-Def — undervoltage UN-G-V1 / V2 110–277 V; 0.01–300 s
User-Def — overfrequency OV-G-F1 / F2 50.1–65 Hz; 0.01–300 s
User-Def — underfrequency UN-G-F1 / F2 45–59.9 Hz; 0.01–300 s
User-Def — Startup-T / Restore-T 10–600 s / 10–600 s
Dimensions W × H × D 691 × 578 × 338 mm
Weight 53.7 kg
Ingress protection IP66
Corrosion resistance C5
Operating temperature −25 to +60 °C
Relative operating humidity 0–100 % RH
Cooling Intelligent fan cooling
Typical noise <55 dB(A)
Maximum altitude 4000 m
Storage temperature −40 to +70 °C
Storage humidity 0–95 % RH, non-condensing
Stacking packaged units Maximum 4 units high
Mounting position Vertical or backward tilt up to 15°
Airflow clearance 500 mm at sides and above floor, 800 mm above enclosure and 1000 mm in front per figure3.1
Mounting structure Firm fire-resistant wall or metal rack with airflow
Mounting — anchors in manual Wall M10 × 90, maximum hole depth 90 mm; rack M10 × 40
Mounting — bracket dimensions 636 × 272 mm; Ø11 mm; 44.5 / 24 / 11 mm
Mounting — bracket / fastening torque 30–35 Nm / 2–3 Nm
Rack mounting — hole and torque Ø12.5 mm / 35 Nm
Handling and lifting points Two people, integrated handles and suitable lifting technique
External earthing Copper 25–50 mm² per connection table, at least half the phase conductor size; external M10 lug, 5–6 Nm
DC cable 4–6 mm²; recommended 4 mm², PV1-F; diameter 5.5–9 mm
DC — stripping length 7 mm
DC — connector torque 3–4 Nm
AC cable Terminal range 10–70 mm²; connection overview 35–70 mm²; recommended 35 mm²
AC — cable outer diameter 37–44 mm; recommended 40 mm
AC — sheath and conductor stripping Sheath about 300 mm; conductor S2 = OT crimp length S1 + 2–3 mm
AC — terminal torque 10–20 Nm
Recommended AC breaker 125 A
Package — inverter / bracket 1 / 1
Package — cross / hex screws 4 × M4 × 14 / 2 × M6 × 12
Package — DC connectors 12
Package — AC cover / 16-pin COM / tool / manual 1 / 1 / 1 / 1
Optional system components Compatible three-phase CT meter, logger and external EPM according to design
Safety IEC / EN 62109-1 / -2
EMC IEC / EN 61000-6-1 / -2 / -3 / -4
Grid standards G99; VDE-AR-N 4105 / VDE V 0124; EN 50549-1; VDE 0126 / UTE C 15 / VFR:2019; RD 1699 / RD 244 / UNE 206006 / UNE 206007-1; CEI 0-21; C10/11; NRS 097-2-1; EIFS 2018.2; IEC 62116 / 61727 / 60068 / 61683; EN 50530
Estimated delivery 2–3 days

Generation for business and industry

S5-GC60K converts module energy for the three-phase supply point of a commercial site, hall or industrial building. Its 60 kW rating describes instantaneous conversion; daily kWh depend on irradiation and array design. The operating system consists of PV modules, grid inverter and connected utility grid. Generation serves local consumption and grid export is managed for the actual connection.

Distributing arrays across MPPTs

6 independent trackers serve up to 12 strings, two per MPPT. Maximum input current is 32 A and short-circuit current 40 A per tracker. Start-up voltage is 195 V, MPPT range 180–1000 V and full-load range 550–850 V. Maximum DC voltage is 1100 V. Each MPPT group uses matching module type and count with corresponding orientation; design checks currents and open-circuit voltage at the local minimum temperature.

Output and efficient conversion

Rated output of 60000 W is complemented by maximum 66000 W and 66000 VA. The manufacturer specifies 100.3 A maximum AC current and 91.2 / 86.6 A rated current at 380/400 V. Connection 3/N/PE uses 220/380 or 230/400 V at 50/60 Hz. Maximum efficiency is 98.7 %, European efficiency 98.3 % and THDi below 3 %. Adjustable power factor supports grid requirements. Transformerless construction has night consumption below 1 W.

Metering for export and consumption

A compatible three-phase meter with external current transformers provides energy-flow data. Terminals 21 A and 22 B of the illustrated meter connect to pins 1 A and 2 B of the 16-pin COM. The manual shows grid-side and load-side metering for export control. A 24-hour overview uses a grid-side meter, enabled 24H Switch and Solis monitoring. Select the meter and transformers for the actual installation.

Output and export management

Internal EPM offers Meter in Load, Meter in Grid and Consumption Monitor. Mode 01 uses average three-phase consumption; mode 02 follows the lowest-loaded phase. Permitted export is configured for the connection design. Configurable failsafe can alarm and stop generation on metering loss. External control supports 5G-EPM or Others-EPM according to the device. Commissioning verifies metering direction and overall response.

Multi-device communication

The 4-pin COM accepts an optional logger for one inverter. The 16-pin COM combines RS485, metering and logic control. Daisy-chain communication uses pins 3/4 as input and 6/7 as output; addresses range 01–99, default 01. The manual lists Wi-Fi, GPRS and LAN loggers and Wi-Fi/GPRS boxes for multiple devices. Communication cable uses 0.75–3 mm² conductors, 4–6 mm diameter and 10–12 mm stripping; the full pinout appears in the technical overview and gallery.

Generation overview and I/V curves

The LCD with capacitive buttons shows MPPT and individual string voltages/currents, output, frequency, energy and operating state. Daily, monthly and yearly history and the latest 100 alarms and 100 warnings are available. Individual-string I/V scanning sets a 100–1100 V start and 1–100 V step with 60 data points. Service menus include fan testing, HMI/DSP updates and output-energy/voltage calibration for grid-operator requirements.

Durable construction and environment

The 691 × 578 × 338 mm enclosure weighs 53.7 kg. IP66 provides dust-tight protection against powerful water jets; C5 corrosion resistance complements suitable indoor or outdoor placement. Intelligent fan cooling supports −25 to +60 °C operation at 0–100 % humidity and altitude up to 4000 m. Typical noise is below 55 dB(A). The site provides airflow and shelter from direct sun. Storage conditions are −40 to +70 °C and 0–95 % non-condensing humidity; packaged units may be stacked up to four high.

Mounting and power terminals

Mount on a fire-resistant wall or metal rack vertically or tilted backward up to 15°. Exact bracket dimensions, clearances and torques appear in the technical overview. Two people and suitable technique use the integrated handles. AC terminals accept M8 lugs, PE uses M6 and the separate external earth point uses M10. Recommended AC conductor size is 35 mm² and this model’s breaker is 125 A. Neutral connection follows local grid requirements. DC uses MC4 and 4–6 mm² copper conductors.

Protection and night-function selection

Integrated protection covers DC polarity, short circuit, AC overcurrent, grid monitoring, anti-islanding and temperature; Type II surge protection is fitted on DC and AC sides. The current matrix listsAFCI 2.0 as optional. Night functions use a selected PID-recovery or Night SVG reactive-power-compensation configuration. The European logic interface uses pins 13 RefGen and 14 Com/DRM0; when enabled under the grid profile, opening the contact reduces output to 0 W within five seconds.

Equipment and matching components

The package includes the inverter, bracket, four M4 × 14 screws, two M6 × 12 screws, 12 DC connectors, AC terminal cover, 16-pin COM connector, unlocking tool and manual. The offer includes the DC switch. Modules, CT meter, logger, protection and mounting components are selected for the whole plant. Design compares kW output with consumption patterns and kWh energy. Any storage uses a separate compatible battery system and appropriate converter. Batterado helps match the components for the connection.

Downloads

AI search description

High-output PV for commercial and industrial sites with flexible array grouping. Solis S5-GC60K delivers 60 kW rated output to a three-phase grid and connects up to 12 strings through 6 independent MPPTs. Each tracker supports 32 A and a 180–1000 V operating range. Up to 98.7 % efficiency, intelligent fan cooling, IP66 and C5 corrosion resistance support demanding installations at suitable locations. String monitoring and I/V scanning provide insight into generation. A compatible meter adds export control and suitable Solis monitoring enables a 24-hour consumption view. The practical 16-pin COM combines metering, multi-inverter communication and logic control. This offer includes the DC switch and standard connection components. S5-GC60K converts module energy for the three-phase supply point of a commercial site, hall or industrial building. Its 60 kW rating describes instantaneous conversion; daily kWh depend on irradiation and array design. The operating system consists of PV modules, grid inverter and connected utility grid. Generation serves local consumption and grid export is managed for the actual connection. The package includes the inverter, bracket, four M4 × 14 screws, two M6 × 12 screws, 12 DC connectors, AC terminal cover, 16-pin COM connector, unlocking tool and manual. The offer includes the DC switch. Modules, CT meter, logger, protection and mounting components are selected for the whole plant. Design compares kW output with consumption patterns and kWh energy. Any storage uses a separate compatible battery system and appropriate converter. Batterado helps match the components for the connection.

Manufacturer: Solis / Ginlong Technologies; Model: S5-GC60K; Type and role: Three-phase grid-connected PV inverter; Offered configuration: Standard 400V model with 6 MPPTs and DC switch; Operating configuration: PV array and three-phase utility grid; Maximum DC voltage: 1100 V; Rated DC voltage: 600 V; Start-up voltage: 195 V; MPPT range: 180–1000 V; Full-load MPPT range: 550–850 V; Maximum input current per MPPT: 32 A / MPPT; Maximum short-circuit current per MPPT: 40 A / MPPT; Independent MPPT count: 6; Maximum PV string count: 12; Strings per MPPT: 2 / MPPT; Rated AC power: 60000 W; Maximum AC power: 66000 W; Maximum apparent AC power: 66000 VA; Grid conductors: 3 / N / PE; Rated grid voltage: 220 / 380 V; 230 / 400 V; Rated frequency: 50 / 60 Hz; Rated current at 380/400 V: 91.2 / 86.6 A; Maximum AC current: 100.3 A; Power factor: >0.99; adjustable 0.8 leading to 0.8 lagging; THDi: <3 %; Maximum efficiency: 98.7 %; European efficiency: 98.3 %; Topology: Transformerless; Night consumption: <1 W; DC polarity protection: Integrated function; Short-circuit protection: Integrated function; AC overcurrent protection: Integrated function; Surge protection: DC Type II / AC Type II; Grid monitoring: Integrated function; Anti-islanding protection: Integrated function; Temperature protection: Integrated function; Multi-peak MPPT scanning: Integrated function; DC switch: Integrated function; AFCI 2.0 arc protection: Optional configuration; DC connectors: MC4; AC terminal connection: OT terminal block up to 70 mm²; L1 / L2 / L3 / N / PE; AC — phase / PE lugs: M8 / M6; AC — neutral connection: With or without neutral according to local grid requirements; Communication: RS485 / USB; Communication connectors: 4-pin COM for data logger; 16-pin COM for RS485, meter and DRM; COM — nut / terminals: 3.5–4 Nm / 0.4–0.6 Nm; 16-pin COM — DRM pins 9–12: 9 DRM1/5; 10 DRM2/6; 11 DRM3/7; 12 DRM4/8; 16-pin COM — supply pins: 15 V+ 12 V; 16 V− GND; 16-pin COM — reserved pins: 5 / 8; RS485 — IN / OUT terminals: 16pin COM: 3 A / 4 B IN; 6 A / 7 B OUT; RS485 — conductor / cable diameter: 0.75–3 mm² / 4–6 mm; COM — conductor stripping: 10–12 mm; Digital meter: Compatible Solis three-phase meter with external CTs according to design; Meter — communication terminals: Meter 21 A / 22 B → pins 1 A / 2 B of 16-pin COM; Remote monitoring: Optional Wi-Fi / GPRS / LAN loggers and Wi-Fi / GPRS box for multiple devices; Inverter monitoring address: 01–99; default 01; LCD display: LCD with capacitive touch buttons; Controls: ESC / UP / DOWN / ENTER; LED indicators: POWER / OPERATION / ALARM; Displayed operating data: PV and phase voltages/currents, power, frequency, energy, status, serial number and version.

Generation history: Daily, monthly and yearly energy; Alarm / warning history: Latest 100 records in each history; Export control: Internal EPM; Meter in Load / Meter in Grid / Consumption Monitor; Export-limit modes: 01 average / 02 according to lowest-loaded phase; 24-hour consumption monitoring: Grid-side meter, 24H Switch and Solis monitoring; Meter failsafe: Configurable alarm and generation stop on metering loss; External EPM: 5G-EPM / Others-EPM according to actual device; Active and reactive power control: Active/reactive output settings and grid working mode; DRM — logic interface: 16pin COM: 13 RefGen / 14 Com/DRM0; DRM — response after opening: Limit to 0 W within 5 s when enabled according to grid profile; Service updates: HMI / DSP; Service compensation settings: Output energy and voltage calibration for grid-operator requirements; String monitoring: Integrated; PID recovery: Optional configuration; Night reactive-power compensation: Night SVG; configuration according to design; Night-function selection: Select PID-recovery or night reactive-power-compensation configuration according to design; I/V curve scanning: Integrated function; I/V scan — start / step / points: 100–1100 V / 1–100 V / 60; Service fan test: Fan Test; User-Def — grid-profile use: Service configuration with grid-operator permission; L–N ranges per manual; User-Def — overvoltage OV-G-V1 / V2: 220–374 V; 0.01–300 s; User-Def — undervoltage UN-G-V1 / V2: 110–277 V; 0.01–300 s; User-Def — overfrequency OV-G-F1 / F2: 50.1–65 Hz; 0.01–300 s; User-Def — underfrequency UN-G-F1 / F2: 45–59.9 Hz; 0.01–300 s; User-Def — Startup-T / Restore-T: 10–600 s / 10–600 s; Dimensions W × H × D: 691 × 578 × 338 mm; Weight: 53.7 kg; Ingress protection: IP66; Corrosion resistance: C5; Operating temperature: −25 to +60 °C; Relative operating humidity: 0–100 % RH; Cooling: Intelligent fan cooling; Typical noise: <55 dB(A); Maximum altitude: 4000 m; Storage temperature: −40 to +70 °C; Storage humidity: 0–95 % RH, non-condensing; Stacking packaged units: Maximum 4 units high; Mounting position: Vertical or backward tilt up to 15°; Airflow clearance: 500 mm at sides and above floor, 800 mm above enclosure and 1000 mm in front per figure3.1; Mounting structure: Firm fire-resistant wall or metal rack with airflow; Mounting — anchors in manual: Wall M10 × 90, maximum hole depth 90 mm; rack M10 × 40; Mounting — bracket dimensions: 636 × 272 mm; Ø11 mm; 44.5 / 24 / 11 mm; Mounting — bracket / fastening torque: 30–35 Nm / 2–3 Nm; Rack mounting — hole and torque: Ø12.5 mm / 35 Nm; Handling and lifting points: Two people, integrated handles and suitable lifting technique; External earthing: Copper 25–50 mm² per connection table, at least half the phase conductor size; external M10 lug, 5–6 Nm; DC cable: 4–6 mm²; recommended 4 mm², PV1-F; diameter 5.5–9 mm; DC — stripping length: 7 mm; DC — connector torque: 3–4 Nm; AC cable: Terminal range 10–70 mm²; connection overview 35–70 mm²; recommended 35 mm²; AC — cable outer diameter: 37–44 mm; recommended 40 mm; AC — sheath and conductor stripping: Sheath about 300 mm; conductor S2 = OT crimp length S1 + 2–3 mm; AC — terminal torque: 10–20 Nm; Recommended AC breaker: 125 A; Package — inverter / bracket: 1 / 1; Package — cross / hex screws: 4 × M4 × 14 / 2 × M6 × 12; Package — DC connectors: 12; Package — AC cover / 16-pin COM / tool / manual: 1 / 1 / 1 / 1; Optional system components: Compatible three-phase CT meter, logger and external EPM according to design; Safety: IEC / EN 62109-1 / -2; EMC: IEC / EN 61000-6-1 / -2 / -3 / -4; Grid standards: G99; VDE-AR-N 4105 / VDE V 0124; EN 50549-1; VDE 0126 / UTE C 15 / VFR:2019; RD 1699 / RD 244 / UNE 206006 / UNE 206007-1; CEI 0-21; C10/11; NRS 097-2-1; EIFS 2018.2; IEC 62116 / 61727 / 60068 / 61683; EN 50530; Estimated delivery: 2–3 days.

Batterado — SOLIS-S5-GC60K

Markdown — SOLIS-S5-GC60K

Additional information

Weight 53,7 kg
Dimensions 33,8 × 69,1 × 57,8 cm

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.

0
0
Your Cart
Your cart is emptyReturn to Shop