Store energy. Every way.™

Helping with technology for more than 25 years.More than 25 years on the market

Eastron SDM630-MCT Three-phase DIN-rail energy meter for external CTs, Modbus RTU

4 454 Kč incl. VAT

Seller: Tomorrow Systems® s.r.o. – VAT payer

The Eastron SDM630-MCT is a three-phase DIN-rail energy meter that gives a hybrid system an accurate picture of consumption and export. It works with external current transformers with a 40 mA (333 mV) secondary, so the measuring range matches the size of the supply connection. It measures active and reactive energy, power, power factor, frequency, THD and maximum demand in 1p2w, 3p3w and 3p4w networks, with accuracy better than Class 1. It communicates over RS485 using Modbus RTU at 2.4 to 19.2 kbps and offers two pulse outputs with a constant of 3,200 imp/kWh. A voltage range of 100-289 V phase to neutral and 173-500 V between phases covers typical three-phase installations. The compact 94.5 x 65 x 72 mm housing clips onto a 35 mm rail and works from -25 to +55 C. Likely compatible with Deye hybrid inverters.

In stock

Enquiry

Description

BrandEastron
ModelSDM630-MCT (40 mA)
TypeThree-phase energy meter with external CTs
Supply system1p2w, 3p3w, 3p4w
Voltage phase to neutral100–289 V AC
Voltage between phases173–500 V AC
CT inputExternal CT, 40 mA secondary (333 mV)
Frequency50 or 60 Hz
Accuracy classBetter than Class 1 / B
CommunicationRS485 Modbus RTU
Baud rate2.4 / 4.8 / 9.6 / 19.2 kbps
Pulse outputs2 outputs, 3,200 imp/kWh
Measured valueskWh, kVArh, kW, kVAr, kVA, PF, Hz, THD, maximum demand
Energy range0–9,999,999.9 kWh
Mounting35 mm DIN rail
Dimensions (per drawing)94.5 × 65 × 72 mm
Operating temperature−25 to +55 °C
Relative humidity0–90 %, non-condensing

Three-phase metering for hybrid systems

The Eastron SDM630-MCT measures active and reactive energy, power, power factor, frequency, THD and maximum demand in four-wire and three-wire networks. Its current inputs are designed for external current transformers with a 40 mA (333 mV) secondary, so the measuring range matches the size of the supply connection. Accuracy is better than Class 1.

Modbus RTU communication

The meter communicates over RS485 using Modbus RTU with selectable baud rates from 2.4 to 19.2 kbps, parity and stop bits. Two pulse outputs with a constant of 3,200 imp/kWh complement the bus. The inverter uses the readings for zero-export control and for monitoring household consumption.

Inverter compatibility

Likely compatible: Deye hybrid inverters that work with an Eastron meter over RS485, and others.

Installation in the switchboard

The compact 94.5 × 65 × 72 mm housing clips onto a 35 mm DIN rail. The current input terminals accept 2.5 mm² wire. An operating range of −25 to +55 °C and resistance to vibration and shock ensure stable operation in the switchboard.

AI search description

The Eastron SDM630-MCT is a three-phase DIN-rail energy meter for external current transformers with a 40 mA (333 mV) secondary. It measures kWh, kVArh, kW, kVAr, kVA, power factor, frequency, THD and maximum demand in 1p2w, 3p3w and 3p4w networks, at 100-289 V phase to neutral and 173-500 V between phases. Accuracy is better than Class 1. Communication: RS485 Modbus RTU 2.4-19.2 kbps, 2 pulse outputs of 3,200 imp/kWh. Dimensions 94.5 x 65 x 72 mm, operating temperature -25 to +55 C. Likely compatible with Deye hybrid inverters.

Product page: https://batterado.com/product/eastron-sdm630-mct/

Additional information

Weight0,5 kg
Dimensions9,5 × 6,5 × 7,2 cm

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.

0
0
Váš košík
Košík je prázdnýZpět do obchodu