| Brand | Victron Energy |
|---|---|
| Model | MultiPlus-II 48/10000/140-100 230V |
| Order code | PMP483105000 |
| Type | Inverter/charger, single-phase |
| Battery voltage class | 48 V |
| DC input voltage range | 38–66 V |
| Continuous output power at 25 °C (VA) | 10,000 VA |
| Continuous output power at 25 °C (W) | 8,000 W |
| Continuous output power at 40 °C | 7,000 W |
| Continuous output power at 65 °C | 6,000 W |
| Max apparent feed-in power | 10,000 VA |
| Peak power | 18,000 W |
| Maximum efficiency | 96 % |
| Zero load power | 38 W |
| Zero load power in AES mode | 27 W |
| Zero load power in Search mode | 4 W |
| AC output voltage | 230 V ± 2 % |
| AC output frequency | 50 Hz ± 0.1 % (can be adjusted to 60 Hz) |
| AC input voltage range | 187–265 V |
| AC input frequency range | 45–65 Hz |
| Maximum AC input current | 100 A |
| Transfer switch | 100 A |
| Switchover time to back-up supply (AC-out-1) | less than 20 ms |
| Auxiliary AC output | Yes (AC-out-2, 50 A) |
| PowerControl & PowerAssist | Yes |
| External AC current sensor (optional) | 100 A |
| Charge voltage: absorption | 57.6 V |
| Charge voltage: float | 55.2 V |
| Charge voltage: storage mode | 52.8 V |
| Maximum battery charge current (up to 25 °C ambient) | 140 A |
| Battery temperature sensor | Not included with 48 V models, order number ASS000001000 |
|---|---|
| Compatible battery chemistries | Lead-acid, lithium and others (charger configurable to the battery manufacturer specifications) |
| Battery connection | Four M8 bolts (2 plus and 2 minus connections) |
| 230 VAC connection | Bolts M6 |
| Programmable relay | Yes (general alarm, DC under voltage or genset start/stop; AC rating 230 V / 4 A, DC rating 4 A up to 35 V and 1 A up to 60 V) |
| Remote on-off | Yes |
| VE.Bus communication port | Yes (for parallel and three-phase operation, remote monitoring and system integration) |
| General-purpose communication port | Yes, 2x |
| Communication protocol: VE.Bus | Yes |
| Bluetooth | Yes, with the optional VE.Bus Smart dongle (VictronConnect) |
| Configuration interface | MK3-USB (RJ45 UTP cable, USB port), VEConfigure software |
| Compatibility: GX devices | Cerbo GX, Ekrano GX |
| Compatibility: monitoring and configuration | VRM Portal and VRM app, VictronConnect (with VE.Bus Smart dongle), VEConfigure with MK3-USB interface, Battery Monitor, Digital Multi Control Panel |
| Compatibility: solar sources | Solar charge controllers and grid-tie inverters |
| Compatible Victron batteries | Victron Lithium Smart with VE.Bus BMS V2 or Lynx Smart BMS; other lithium batteries per the Victron battery compatibility list and others |
| ESS (Energy Storage System) | Yes, grid code selected with the VEConfigure tool |
| Parallel operation | Up to 6 units, only with an external AC transfer switch |
| Three-phase operation | Three units of the same model |
| Enclosure | Steel, blue RAL 5012 |
| Protection category | IP22 |
| Operating temperature range | −40 to +65 °C (fan-assisted cooling) |
| Humidity (non-condensing) | max 95 % |
| Maximum altitude | 2000 m |
| Weight | 49 kg |
| Dimensions (h × w × d) | 677 × 363 × 206 mm |
| Protection | Output short circuit, overload, battery voltage too high, battery voltage too low, temperature too high, 230 V AC on inverter output, input voltage ripple too high |
| Optional accessories | Digital Multi Control Panel, VE.Bus Smart dongle, MK3-USB interface, current sensor 100 A:50 mA |
| Standards: safety | EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2 |
| Standards: EMC (emission, immunity) | EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3 |
10 kVA inverter/charger for 48 V systems
The Victron Energy MultiPlus-II 48/10000/140-100 230V is a single-phase inverter with a built-in battery charger and transfer switch in one steel enclosure. It works with 48 V batteries (DC input voltage range 38–66 V) and delivers 230 V ± 2 % at 50 Hz ± 0.1 % on the output (can be switched to 60 Hz). Continuous output power is 10,000 VA / 8,000 W at 25 °C, 7,000 W at 40 °C and 6,000 W at 65 °C. Peak power reaches 18,000 W and maximum efficiency is 96 %.
The model has all the features of the MultiPlus range plus the option of an external current sensor that extends the PowerControl and PowerAssist functions to 100 A. It is suited to professional marine, yachting, vehicle and land-based off-grid applications. It includes anti-islanding functionality and an increasingly long list of country approvals for ESS applications.
No-break back-up supply and two AC outputs
The main output AC-out-1 has no-break functionality. When the grid fails or a generator or shore power is disconnected, the inverter takes over the supply to the connected loads in under 20 ms. Computers and other electronic equipment therefore keep operating without disruption, and the unit can also serve as an emergency power system in industrial and telecommunication applications.
The second output AC-out-2 is live only when voltage is present on the AC input. In battery operation its load is disconnected immediately. It suits loads that should not discharge the battery, for example a water heater, an electric boiler or an air conditioner. When input voltage returns, the load on AC-out-2 is reconnected after a delay of approximately 2 minutes so that a generator can settle. The auxiliary output is rated at 50 A.
PowerControl and PowerAssist
With PowerControl a maximum current from the grid or generator can be set. The inverter then takes other AC loads into account and uses only the surplus current for charging the battery, so it does not overload the generator or the shore connection.
PowerAssist goes further. Peak power is often needed only for a short time, and when the load exceeds the capacity of the generator, shore connection or grid, the inverter immediately supplements the missing power from the battery. When the load drops, the spare power is used to recharge the battery. The function suits any place where peaks are short, for example when starting motors or cooking.
Charger and battery side
The charger is microprocessor-controlled and uses an adaptive four-stage algorithm (bulk – absorption – float – storage). The absorption time adapts to how deeply the battery was discharged. Charge voltages are 57.6 V (absorption), 55.2 V (float) and 52.8 V (storage). The maximum battery charge current is 140 A at up to 25 °C ambient.
Solar energy, ESS and GX devices
The inverter can be operated off-grid as well as in grid-connected systems with PV and other alternative energy sources. It is compatible with solar charge controllers and with grid-tie inverters. When a solar inverter is connected to the output, surplus solar energy charges the battery. Once the absorption voltage is reached, the charge current is reduced and surplus energy is fed back into the grid. If the grid is not available, the inverter slightly raises the AC frequency to reduce the output of the solar inverter, so AC power stays available even during a grid failure.
For feeding energy back into the grid (ESS, Energy Storage System), the appropriate grid code country setting must be selected in the VEConfigure tool. Once set, a password is required to disable grid code compliance or change related parameters. The maximum apparent feed-in power is 10,000 VA. The system can be complemented with a Cerbo GX or Ekrano GX, which provide intuitive control and monitoring and give access to the VRM portal.
Choosing a battery and communication
The inverter is designed for 48 V batteries (DC 38–66 V), lead-acid as well as lithium. For Victron Lithium Smart batteries use the VE.Bus BMS V2 or the Lynx Smart BMS. For other lithium batteries follow the Victron list of compatible battery types, which also gives installation and configuration instructions. Other batteries are supported too.
The inverter has two general-purpose programmable ports (Aux in 1 and Aux in 2) which can be used, among other things, for communication with the BMS of a lithium-ion battery, and a VE.Bus communication port for parallel and three-phase operation, remote monitoring and system integration. Settings are made in the VictronConnect app or in VEConfigure software. At 48 V the currents are considerable: the charge current reaches 140 A. Choose a battery whose permitted charge and discharge currents match this, and size the cabling and fuses according to the battery documentation.
Parallel and three-phase operation
Up to 6 units can be connected in parallel for higher power. The 8k, 10k and 15k models can be connected in parallel only with an external AC transfer switch. Six 48/10000/140-100 units therefore give 48 kW / 60 kVA and a charging capacity of 840 A. Three units of the same model can also be configured for three-phase output.
Installation: dimensions, connections, protection category
The inverter has a steel enclosure in blue RAL 5012 with protection category IP22. Cooling is fan-assisted and the operating temperature range is −40 to +65 °C. Humidity may be up to 95 % non-condensing and the maximum altitude is 2000 m. Dimensions (h × w × d) are 677 × 363 × 206 mm and weight is 49 kg, so allow for a suitable load capacity of the mounting surface.
The battery is connected with four M8 bolts (two plus and two minus connections), and the AC wiring with M6 bolts. An earth leakage circuit breaker and a fuse or circuit breaker rated for the expected load must be installed in series with the AC output, and the cable cross-section is chosen accordingly.
Operation and monitoring: VRM and VictronConnect
Settings can be changed in a matter of minutes with VEConfigure software. You need a computer and an MK3-USB interface, which connects to the inverter with an RJ45 UTP cable and plugs into a USB port. Bluetooth communication with the VictronConnect app is provided by the optional VE.Bus Smart dongle, which also measures battery voltage and temperature. Monitoring and control are possible with the Cerbo GX, Ekrano GX, a laptop or computer, the Battery Monitor and the Digital Multi Control Panel, a convenient solution with an on/off/charger-only switch, a full LED readout and a rotary knob to set the PowerControl and PowerAssist levels.
Once a GX device is connected to the internet, operational data is stored and displayed on the VRM (Victron Remote Management) website free of charge, and settings can be changed remotely. Alarms can be received by e-mail or push notification. A VRM app for iOS and Android is also available.
AI search description
The Victron Energy MultiPlus-II 48/10000/140-100 230V, order code PMP483105000, is a 10 kVA single-phase inverter/charger for 48 V batteries (DC 38–66 V). Continuous output at 25 °C is 10,000 VA / 8,000 W, peak 18,000 W, charge current up to 140 A, efficiency up to 96 %. Two AC outputs (AC-out-1 with switchover in under 20 ms, AC-out-2 only when AC input is available), PowerControl and PowerAssist, VE.Bus communication. Compatible with the GX devices Cerbo GX and Ekrano GX, the VRM portal, the VictronConnect app and Victron Lithium Smart batteries. Use: back-up power, ESS, PV systems. Dimensions 677 × 363 × 206 mm, 49 kg, IP22.
Product page: https://batterado.com/product/victron-multiplus-ii-48-10000-140-100/













Reviews
There are no reviews yet.