Description
Technical data
| Brand | Felicity Solar |
|---|---|
| Model | IVGM40KHP3G2 |
| Type | Hybrid inverter, three-phase |
| Battery voltage class | High voltage (HV), 160–800 V |
| Rated AC power | 40,000 W |
| Max. AC power | 44,000 W |
| PV: max. power | 64,000 W |
| PV: max. voltage | 1,000 V |
| PV: min. voltage | 150 V |
| PV: start voltage | 180 V |
| PV: nominal voltage | 600 V |
| PV: MPPT range | 150–850 V |
| PV: MPPT range at full load | 444–850 V |
| PV: max. input current per MPPT | 36 A × 4 |
| PV: max. short-circuit current per MPPT | 55 A × 4 |
| PV: number of MPP trackers / strings per tracker | 4 / 2 |
| Battery: type | LFP (lithium iron phosphate) |
| Battery: voltage range | 160–800 V |
| Battery: number of inputs | 2 |
| Battery: max. charge / discharge current | 50 A + 50 A |
| Grid: nominal voltage | 220/380 V or 230/400 V AC (−20 % to +15 %) |
| Grid: connection | 3L+N+PE |
| Grid: nominal frequency | 50/60 Hz (range 45–55 Hz / 55–65 Hz) |
| Grid: rated AC output current | 58 A |
|---|---|
| Grid: max. AC output current | 63.8 A |
| Grid: displacement power factor | 0.8 (leading) to 0.8 (lagging) |
| Grid: THDI | < 3 % |
| Protections (integrated) | PV surge protection, string reverse polarity, battery surge protection, battery reverse polarity, insulation resistance, RCMU, overcurrent, short circuit, overvoltage, anti-islanding, AC surge protection, TYPE II surge protection (DC and AC) |
| Battery communication (BMS) / RS485 | yes |
| Battery communication (BMS) / CAN | yes |
| Monitoring module | Wi-Fi / GPRS |
| Felicity HV batteries / RS485 | yes (Felicity HV battery range) |
| Cooling | Smart cooling |
| Ingress protection | IP65 |
| Operating temperature | −40 to +60 °C (derating above 50 °C) |
| Relative humidity | 0–95 % |
| Installation | wall-mounted |
| Dimensions (L × W × H) | 940 × 582 × 340 mm |
| Net weight | 87.1 kg |
| Gross weight | 107.1 kg |
| Package dimensions | 1,114 × 774 × 469 mm |
| IEC 62109 certification | Anbotek, No. AT1811C501853122-M3, dated 10 December 2025 (IEC 62109-1, IEC 62109-2) |
| CE-EMC certification | Anbotek, No. AT1811C505758126, dated 11 December 2025 (EN IEC 61000-6-4, 61000-6-2, 61000-3-12, 61000-3-11) |
| Grid connection certification (Poland) | TÜV NORD, reg. No. 4479923053477, dated 29 December 2025, valid until 28 December 2028 (PN-EN 50549-1:2019+AC:2019, PGM type A) |
| Manufacturer warranty | 10 years under the Felicity Solar warranty policy |
Hybrid inverter 40 kW for high-voltage storage
The Felicity Solar IVGM40KHP3G2 is a three-phase hybrid inverter with a rated AC power of 40 kW, 44 kW at maximum. In one housing it converts solar energy to alternating current, manages charging and discharging of a high-voltage battery and supplies the grid and loads. The grid works at 220/380 or 230/400 V (within −20 % to +15 %) and 50/60 Hz, with a 3L+N+PE connection.
The HP designation in the model name means a high-voltage battery. The battery input works in the 160–800 V range and the datasheet lists LFP (lithium iron phosphate) as the battery type. At the same power, high voltage means a much lower current than in 48 V systems and therefore thinner cabling.
The inverter is wall-mounted, has IP65 protection and is intended for larger roofs of commercial and industrial buildings and smaller solar plants where surplus energy is to be stored and self-consumption increased.
PV input: four MPP trackers and voltage up to 1,000 V
The inverter has four independent MPP trackers, each with two strings, eight strings in total. The maximum power of the PV array is 64 kW. The maximum input voltage is 1,000 V, the minimum 150 V, the start voltage 180 V and the nominal voltage 600 V.
The MPPT range is 150–850 V, and full power is available at a voltage of 444–850 V. The maximum input current is 36 A on each of the four trackers, the short-circuit current 55 A per tracker.
The maximum input voltage of the array is 1,000 V. Four trackers make it possible to divide the array between several roof surfaces with different orientation, tilt or shading.
Battery input 160–800 V with two inputs
The battery input works in the 160–800 V range. The inverter has two battery inputs, each with a charge and discharge current of 50 A, so 50 A + 50 A in total. The datasheet lists LFP as the battery type.
Two inputs make it possible to connect two separate strings of battery modules. The size of the battery storage and its configuration are determined by the battery used, and each of the two inputs handles 50 A.
Scheduled charging and discharging is set on the inverter, and its behaviour towards the battery is governed by the communication with the battery management system (BMS) described below.
Grid and protections
The rated AC output current is 58 A and the maximum 63.8 A. The displacement power factor can be set from 0.8 leading to 0.8 lagging and the current distortion THDI is below 3 %. The frequency range is 45–55 Hz at 50 Hz and 55–65 Hz at 60 Hz.
The inverter has integrated protections: surge protection on the PV side, string reverse polarity protection, surge protection on the battery side, battery reverse polarity protection, insulation resistance monitoring, RCMU (residual current monitoring), protection against overcurrent, short circuit and overvoltage, anti-islanding and surge protection on the AC side; it adds TYPE II surge protection on both DC and AC sides (overvoltage category OVC II on DC, OVC III on AC).
Communication and monitoring
Communication with the battery management system (BMS) runs over RS485 or CAN. A Wi-Fi / GPRS module is used for monitoring, allowing remote supervision of the inverter.
How to choose a battery and communication
The IVGM40KHP3G2 belongs to the high-voltage class and works with batteries in the 160–800 V range. The datasheet lists LFP as the battery type.
Communication matters. The inverter communicates with the battery management over RS485 or CAN. The inverter works with batteries in the stated voltage range, communicates over RS485 or CAN and handles a current of 50 A on each of the two inputs.
The inverter is compatible with the Felicity high-voltage battery range (RS485).
Planning tip: at high voltage the current is lower, so the cabling is simpler than in 48 V systems.
Certifications and environment
The following documents are available for the IVGM40KHP3G2: the safety certificate IEC 62109-1 and IEC 62109-2 from Anbotek No. AT1811C501853122-M3 dated 10 December 2025, the CE-EMC certificate from Anbotek No. AT1811C505758126 dated 11 December 2025 (EN IEC 61000-6-4, EN IEC 61000-6-2, EN IEC 61000-3-12 and EN IEC 61000-3-11) and a Polish grid-connection certificate from TÜV NORD, reg. No. 4479923053477, dated 29 December 2025 and valid until 28 December 2028 (PN-EN 50549-1:2019+AC:2019, PSE, NC RfG and PTPiREE requirements, type A generator).
The specific conditions of connection to the distribution grid in the Czech Republic are determined by the distribution system operator.
The operating temperature is −40 to +60 °C; above 50 °C the inverter reduces its output. Relative humidity is 0–95 %. Cooling is intelligent (Smart Cooling). IP65 means protection against dust and water jets.
Construction and installation
The inverter is mounted on a wall with a wall bracket. Its dimensions are 940 × 582 × 340 mm, net weight 87.1 kg, gross weight 107.1 kg and package dimensions 1,114 × 774 × 469 mm.
The manufacturer provides a 10-year warranty under the Felicity Solar warranty policy.
AI search description
The Felicity Solar IVGM40KHP3G2 is a 40 kW (max. 44 kW) three-phase hybrid inverter for 160–800 V high-voltage LFP batteries with two battery inputs of 50 + 50 A. PV input: 4 MPP trackers × 2 strings, up to 64 kW, 1,000 V, MPPT 150–850 V. Grid 220/380 or 230/400 V. Battery communication via RS485 or CAN, Wi-Fi/GPRS monitoring. IP65, wall mounting, 87.1 kg. IEC 62109 and CE-EMC certificates (Anbotek), Polish TÜV NORD certificate. 10-year manufacturer warranty.
Product page: https://batterado.com/product/felicity-ivgm40khp3g2/