Description
Technical specifications
| Manufacturer | Huawei |
|---|---|
| Model | SUN2000-100KTL-M2 |
| Type and role | Three-phase grid-connected PV string inverter |
| Rated AC output | 100 kW |
| Maximum apparent AC power | 110000 VA |
| Maximum active power cosφ=1 | 110000 W |
| Grid voltage | 220/380 V /230/400 V /277/480 V /3L+(N)+PE |
| Grid frequency | 50 /60 Hz |
| Maximum AC current per current manual | 160.4 A /400 V AC |
| Power factor | 0.8 leading…0.8 lagging |
| THD at rated power | <3 % |
| Maximum DC voltage | 1100 V |
| Startup voltage | 200 V |
| MPPT range | 200–1000 V |
| Full-load MPPT range | 540–800 V /400 V AC |
| Rated DC voltage | 600 V /400 V AC |
| MPPT count | 10 |
| PV string count | 20 |
| Strings per MPPT | 2 |
| Current per MPPT | 30 A |
| Short-circuit current per MPPT | 40 A |
| Maximum efficiency | ≥98.6 % /400 V AC |
| European efficiency | ≥98.4 % /400 V AC |
| Ingress protection | IP66 |
| Operating temperature | −25…+60 °C |
| Operating relative humidity | 0–100 % |
| Operating altitude | 0–5000 m, output derating above 4000 m |
| Weight including hanging kits | ≤93 kg |
| Dimensions W × H × D | 1035 ×700 ×365 mm |
| Cooling | Smart air cooling |
| Topology | Transformerless |
| Local operation | LED /USB data cable +App |
| Standard communication | RS485 /MBUS /USB |
| Ethernet connection | With compatible WLAN-FE Smart Dongle |
| Mobile data connection | Optional compatible 4G Smart Dongle |
| System monitoring | SmartLogger3000 /5000B /SmartMGC5000B /Smart Dongle according to design |
| Energy metering | DTSU666-HW /YDS60-80 /DHSU1079-ZT /DTSU71C according to firmware and layout |
| DC switch | Supported |
|---|---|
| Anti-islanding protection | Supported |
| DC reverse-polarity protection | Supported |
| Insulation monitoring | Supported |
| Residual current monitoring | Supported |
| AC overcurrent | Supported |
| AFCI | Supported |
| DC surge protection | Type II |
| AC surge protection | Type II |
| Overvoltage category | PV II /AC III |
| Reference AC breaker | 250 A /≥500 V AC /3-phase |
| DC conductors | 4–6 mm² Cu |
| AC conductors | 70–240 mm² Cu |
| PE conductor | Sp ≥S/2 /IEC60364-5-54 |
| RS485 conductors | 0.25–1 mm² outdoor shielded twisted pair |
| Grid systems | TN-S /TN-C /TN-C-S /TT /IT |
| Safety standards | EN/IEC62109-1 /EN/IEC62109-2 |
| Installation | Fixed wall installation |
| Offer content | Individual PV inverter |
| Estimated delivery | 2–3 days, seller estimate |
| AC aluminum conductors per design | 95–240 mm² /Al alloy /Cu-clad Al |
| PV string monitoring | Supported |
| Maximum efficiency at 480 V | ≥98.8 % |
| Rated DC voltage at 480 V AC | 720 V |
| Full-load MPPT at 480 V AC | 625–850 V |
| Single-string current | 20 A |
| DC connector | Amphenol Helios H4 or Staubli MC4 according to factory variant |
| AC connector | Waterproof connection with OT/DT terminals |
| DC cable outer diameter | 5.5–9 mm |
| European efficiency at 480 V | ≥98.6 % |
| AC single-core cable | 14–32 mm outer diameter |
| AC multi-core cable | 24–66 mm outer diameter |
| AC cable lugs | M12 OT/DT |
| PE cable lugs | M10 OT/DT |
| MBUS communication | With appropriate system and isolation equipment |
| Night consumption per datasheet | <3.5 W |
| Smart string disconnection per datasheet | Supported |
Solar generation for rooftops and businesses
Huawei SUN2000-100KTL-M2 is a 100 kW three-phase grid-connected PV inverter for commercial rooftops, industrial sites and larger solar plants. Ten independent MPPTs and twenty string inputs divide the array into clear electrical branches. IP66 protection, smart air cooling and system monitoring suit a fixed engineered installation.
AC power and energy generation
Rated AC output is 100 kW and maximum apparent power is 110000 VA according to the model specification and selected grid profile. Generation in kWh depends on site, modules, orientation, shading and operating conditions. For a 400 V grid, the current manual lists ≥98.6% maximum and ≥98.4% European efficiency.
Ten MPPTs and twenty string inputs
Ten MPPTs serve twenty inputs, with up to two strings per tracker. Maximum current is 30 A per MPPT, 20 A per individual string and 40 A MPPT short-circuit current. Startup voltage is 200 V and the operating range is 200–1000 V. Full-load MPPT is 540–800 V at 400 V AC and 625–850 V at 480 V AC. Strings sharing a tracker are designed with matching modules and counts.
Operating environment
The manufacturer specifies −25 to +60°C operation, IP66 protection and 0–100% relative humidity. The current manual lists operation up to 5000 m with output derating above 4000 m. Design considers the temperature characteristic, airflow and installation clearances.
Dimensions and cooling
Dimensions are 1035 ×700 ×365 mm and manufacturer-specified weight is no more than 93 kg. Smart air cooling is planned with the specified airflow access. Fixed installation requires an appropriate supporting structure and access to the maintenance compartment, AC terminals, DC inputs and communication interface.
System configuration
The installation combines correctly sized PV strings, the grid inverter, AC protection, distribution equipment and the utility connection. Metering and control are selected for the project and grid requirements. Where the building also uses storage, its own power and control branch is assessed as a separate part of the energy-system design.
Monitoring and communication
LED indicators and a USB data connection with the app support local commissioning. RS485 and MBUS provide system connectivity; MBUS is designed with the appropriate isolation and control equipment. Monitoring uses SmartLogger3000, SmartLogger5000B, SmartMGC5000B or a compatible Smart Dongle according to the project. Recommended metering includes DTSU666-HW, YDS60-80, DHSU1079-ZT or DTSU71C matched to the configuration.
Protection and optimization
The model supports PV-string, insulation and residual-current monitoring, DC polarity protection, AC overcurrent protection and grid-operation protection. DC and AC surge protection is specified as Type II. The exact factory version and protection arrangement are checked against documentation and the project design. For the 100KTL-M2, the datasheet also specifies AFCI and smart string disconnection.
Protection and cable design
The manual gives a reference three-phase 250 A AC breaker rated at least 500 V AC. Copper AC conductors range from 70–240 mm²; suitable aluminum-alloy or copper-clad aluminum conductors from 95–240 mm². AC lugs are M12 OT/DT and PE lugs M10 OT/DT. For the same conductor material, reference PE cross-section is at least half the AC cross-section; other combinations are sized for equivalent conductivity according to the manual and IEC60364-5-54. DC conductors are 4–6 mm² and RS485 conductors 0.25–1 mm².
Model selection and building demand
The 100 kW version is selected for the array, grid connection, load profile and generation-control rules. Ten MPPTs divide a larger array into independently tracked sections. Power in kW, generation in kWh, individual string currents and grid capacity are assessed separately.
Offer scope and documentation
The offer covers the exact individual inverter model shown. Modules, metering, logger, protection and other project components are selected for the installation. The public Markdown profile contains model-specific specifications and the appropriate system role. Estimated delivery of 2–3 days is the seller’s estimate.
Downloads
AI search description
Huawei SUN2000-100KTL-M2 — 100 kW three-phase grid inverter. Huawei SUN2000-100KTL-M2 is a 100 kW three-phase grid-connected PV inverter for commercial rooftops, industrial sites and larger solar plants. Ten independent MPPTs and twenty string inputs divide the array into clear electrical branches. IP66 protection, smart air cooling and system monitoring suit a fixed engineered installation. The installation combines correctly sized PV strings, the grid inverter, AC protection, distribution equipment and the utility connection. Metering and control are selected for the project and grid requirements. Where the building also uses storage, its own power and control branch is assessed as a separate part of the energy-system design.
Manufacturer: Huawei; Model: SUN2000-100KTL-M2; Type and role: Three-phase grid-connected PV string inverter; Rated AC output: 100 kW; Maximum apparent AC power: 110000 VA; Maximum active power cosφ=1: 110000 W; Grid voltage: 220/380 V /230/400 V /277/480 V /3L+(N)+PE; Grid frequency: 50 /60 Hz; Maximum AC current per current manual: 160.4 A /400 V AC; Power factor: 0.8 leading…0.8 lagging; THD at rated power: <3 %; Maximum DC voltage: 1100 V; Startup voltage: 200 V; MPPT range: 200–1000 V; Full-load MPPT range: 540–800 V /400 V AC; Rated DC voltage: 600 V /400 V AC; MPPT count: 10; PV string count: 20; Strings per MPPT: 2; Current per MPPT: 30 A; Short-circuit current per MPPT: 40 A; Maximum efficiency: ≥98.6 % /400 V AC; European efficiency: ≥98.4 % /400 V AC; Ingress protection: IP66; Operating temperature: −25…+60 °C; Operating relative humidity: 0–100 %; Operating altitude: 0–5000 m, output derating above 4000 m; Weight including hanging kits: ≤93 kg; Dimensions W × H × D: 1035 ×700 ×365 mm; Cooling: Smart air cooling; Topology: Transformerless; Local operation: LED /USB data cable +App; Standard communication: RS485 /MBUS /USB; Ethernet connection: With compatible WLAN-FE Smart Dongle; Mobile data connection: Optional compatible 4G Smart Dongle; System monitoring: SmartLogger3000 /5000B /SmartMGC5000B /Smart Dongle according to design.
Energy metering: DTSU666-HW /YDS60-80 /DHSU1079-ZT /DTSU71C according to firmware and layout; DC switch: Supported; Anti-islanding protection: Supported; DC reverse-polarity protection: Supported; Insulation monitoring: Supported; Residual current monitoring: Supported; AC overcurrent: Supported; AFCI: Supported; DC surge protection: Type II; AC surge protection: Type II; Overvoltage category: PV II /AC III; Reference AC breaker: 250 A /≥500 V AC /3-phase; DC conductors: 4–6 mm² Cu; AC conductors: 70–240 mm² Cu; PE conductor: Sp ≥S/2 /IEC60364-5-54; RS485 conductors: 0.25–1 mm² outdoor shielded twisted pair; Grid systems: TN-S /TN-C /TN-C-S /TT /IT; Safety standards: EN/IEC62109-1 /EN/IEC62109-2; Installation: Fixed wall installation; Offer content: Individual PV inverter; Estimated delivery: 2–3 days, seller estimate; AC aluminum conductors per design: 95–240 mm² /Al alloy /Cu-clad Al; PV string monitoring: Supported; Maximum efficiency at 480 V: ≥98.8 %; Rated DC voltage at 480 V AC: 720 V; Full-load MPPT at 480 V AC: 625–850 V; Single-string current: 20 A; DC connector: Amphenol Helios H4 or Staubli MC4 according to factory variant; AC connector: Waterproof connection with OT/DT terminals; DC cable outer diameter: 5.5–9 mm; European efficiency at 480 V: ≥98.6 %; AC single-core cable: 14–32 mm outer diameter; AC multi-core cable: 24–66 mm outer diameter; AC cable lugs: M12 OT/DT; PE cable lugs: M10 OT/DT; MBUS communication: With appropriate system and isolation equipment; Night consumption per datasheet: <3.5 W; Smart string disconnection per datasheet: Supported. LED indicators and a USB data connection with the app support local commissioning. RS485 and MBUS provide system connectivity; MBUS is designed with the appropriate isolation and control equipment. Monitoring uses SmartLogger3000, SmartLogger5000B, SmartMGC5000B or a compatible Smart Dongle according to the project. Recommended metering includes DTSU666-HW, YDS60-80, DHSU1079-ZT or DTSU71C matched to the configuration.













Reviews